High Performance Controllers & Programmers
Overview
.gif)
Technical Specification
Environmental performance
Temperature limits Operation: 0 to 50°CStorage: -10 to 70°C
Humidity limits Operation: 5 to 95% RH non condensing
Storage: 5 to 95% RH non condensing
Panel sealing: IP65, Nema 4X
Vibration: 2g peak, 10 to 150Hz
Altitude: <2000 metres
Atmospheres: Not suitable for use in explosive or
corrosive atmosphere
Physical
Panel mounting: 1/4 DIN
Dimensions and weight: 96W x 96H x 150D mm, 600g
Panel cut-out dimensions: 92W x 92Hmm
Control options
No. of loops: 1, 2 or 3 loops
Options: Cascade, Ratio or Override
Modes: PID, ON/OFF or Valve Position
Applications: Carbon Potential, Humidity
Approvals
CE, cUL listed (file E57766), Gost
Suitable for use in Nadcap and
AMS2750D applications under System
Accuracy Test calibration conditions
Standard I/O
Precision PV input
Accuracy: ±0.1%
Ranges: mV, mA, volts or RTD (PT100)
Thermocouple types: J, K, l, N, R, S, B, PII, C, plus others
Cold junction: Ext 0°C, 45°C or 50°C
Analogue input
Allocation: 1 fitted
Accuracy: ± 0.1%
Ranges: -10V to 10V or 0 to 20mA
Digital I/O
Types: 1 digital input
7 Bi-directional input/outputs
1 Changeover relay
Modules
Digital outputs
Types: Single Relay, Dual Relay, Single Triac,
Dual Triac, Single Logic and Triple Logic
module
Allocation: Slot 1, 3, 4, 5 or 6 (Max 3 Triacs
per unit)
Digital inputs
Types: Triple contact input, Triple logic input
Allocation: Slot 1, 3, 4, 5 or 6
Analogue outputs
Types: DC Control or DC
Retransmission (5 Max)
Allocation: Slot 1, 3, 4, 5 or 6
Range: 0 to 20mA or 0 to 10Vdc
Dual Analogue outputs
Allocation: Slot 1, 4 or 5
Range: 4-20mA or 24Vdc transmitter PSU
High Resolution Analogue output
Allocation: Slot 1, 4 or 5
Range: 4-20mA and 24Vdc transmitter PSU
Transmitter PSU
Allocation: Slot 1, 3, 4, 5 or 6
Transmitter: 24Vdc @ 20mA
Transducer supply
Bridge voltage: Software selectable, 5 or 10Vdc
Bridge resistance: 300Ω to 15Kohms
Potentiometer input
Potentiometer resistance 330Ω to 150kohms
Precision PV input (Module)
Allocation: Slot 3 or 6
Accuracy: ±0.1%
Ranges: mV, mA, volts or RTD (PT100)
Thermocouple types: J, K, T, L, N, R, S, B, PII, C, plus others
Cold junction: Ext 0°C, 45°C or 50°C
Dual (Probe) input
Allocation: Slot 3 or 6
Accuracy: ±0.1%
Ranges: mV, mA, volts or RTD (PT100)
Thermocouple types: J, K, T, L, N, R, S, B, PII, C, plus others
Cold junction: Ext 0°C, 45°C or 50°C
Analogue input (module)
Allocation: Slot 1, 3, 4 or 6
Accuracy: ±0.2%
Ranges: mV, mA, volts or RTD (PT100)
Thermocouple types: J, K, T, L, N, R, S, B, PII, C, plus others
Cold junction: Ext 0°C, 45°C or 50°C
Setpoint Programmer
No profiles: 1, 2 or 3 profiles
No. of programs: 50 programs max.
No. of segments: 500 time to target segments (max.) or
400 ramp rate segments (max.)
Event outputs: Up to 16
I/O Expander
10 I/O version: 4 Changeover and 6 normally open relay
contacts
10 Logic inputs
20 I/O version: 4 Changeover and 16 normally open
contacts
20 Logic inputs
Advanced Functions
Application blocks: 32 digital operations
24 analogue operations
12 user values
Timers: 4 ON pulse, OFF delay, one shot and
min-ON
Totalisers: 4, trigger level and reset input
Pattern generators: 16 patterns each with 16 bits
Real time clock: Day of the week and time
Customisable screens: 8 user screens
User switches: 8, toggle and momentary function
Slave communications
Allocation: Slot H or J (DeviceNet/Profibus slot H
only)
Types: Profibus DP RS485
Modbus RTU RS485 (2 wire)
RS485 (5 wire) or RS232
DeviceNet
EI-Bisyc (subset of parameters)
Master communications
Allocation: Slot J
Types: Modbus RTU RS485 (2 wire),
RS485 (4 wire) or RS232
Parameters: 25 read/write